35 of 36 © 2007 D 423 - 08/07
Error Messages (5 of 5)
Error Message Description
tekmar STAGER SETTING CONFLICT
There is a DIP switch settings conflict. The tekmar Stager DIP switch is set to On and the
Boiler Sensor DIP switch is set to Ret. Once the Boiler Sensor DIP switch is set to Sup or the
tekmar Stager DIP switch is set to Off, the error message clears.
DEVICE ERROR AT ADDRESS #:##
#:## is the address of the device with the error. The bus number displays before the colon,
and the device number displays after. Go to the device with the address displayed.
Possible Addresses:
b:01 to b:24 - Device Error on Boiler Bus
1:01 to 1:24 - Device Error on Bus 1
2:01 to 2:24 - Device Error on Bus 2
3:01 to 3:24 - Device Error on Bus 3
Comentarios a estos manuales