3 of 4 Copyright © 1999 U 363 -06/99
Room Temperature Unit (RTU) 062, 063
A single RTU can be connected to the mixed side (tN1/tN2) of the Universal Reset Control 363 in order to
provide a one zone mixed water temperature system. When multiple zones are required for the mixed side,
use either a tekmar zone control or, through the mix demand input, on / off zone control. When using an RTU,
several items related to the mixing side of the heating system are no longer available in the control’s display.
These items will be available only in the RTU’s display. Also, the number of items that are available on the
RTU will depend on the type of RTU (062 or 063) that is connected to the control.
35 to 100˚F
(2 to 38˚C)
Current room air temperature.
14 to 167˚F
(-10 to 75˚C)
Target room air temperature.
-67 to 149°F
(-55 to 65°C)
Current slab sensor temperature. This item is only available if a
tekmar slab sensor is connected to a RTU 063.
-58 to 167°F
(-50 to 75°C)
363 RTU View Menu
Item
LTD
USER
Range
062
063
• • • •
• • •
• • • •
• •
Current outdoor air temperature as measured by the outdoor sensor.
ItemMenu
UnOcc 1
°
F
View
Heat
The units of measure that all of the temperatures are to be displayed
in by the control.
˚F, ˚C
•
•
The operating mode for the back lighting of the LCD and the time
until the control returns to the view menu after any button was
pressed.
If
Backlight is set to
OFF
,
the control returns after 10
seconds and the backlight stays off.
If Backlight is set to
30 SEC
,
the control returns after 30 seconds and the backlight stays on for
30 seconds after any button press.
If Backlight is set to
ON
,
the
control returns after 90 seconds and the backlight stays on.
OFF, 30 sec, ON
• •
The access level that is to be used by the control.
DIP switch =
Only qualified service people should adjust items in the
ADV
(Advance)
and
INST
(Installer) access levels.
ADV, INST, USER, LTD
363 Misc (Miscellaneous) Menu
Item
LTD
USER
Range
NONE
,
TMPY
Occ,
PERM
Occ,
TMPY
UnOcc,
PERM
UnOcc,
AWAY
• •
363 Schd (Schedule) Menu
Item
LTD
USER
Range
None
– No override.
TMPY Occ
– Overrides to Occupied setting for 3 hours.
PERM Occ
– Overrides to Occupied setting until new
override is selected.
TMPY UnOcc
- Overrides to UnOccupied for 3 hours.
PERM UnOcc
– Overrides to UnOccupied setting until
new override is selected.
AWAY
– Room & WWSD temperature at 62˙F (17˙C), no DHW.
The type of setback override that is in effect.
DIP switch =
Setback
AWAY is available even if DIP ≠ Setback
Note: Depending on the settings the installer make in the control, certain menu items may not appear.
-67 to 149˚F
(-55 to 65˚C)
-67 to 149˚F
(-55 to 65˚C)
The highest DHW tank or Storage tank temperature since this item
was last cleared. To clear this item, press both the and buttons
until ‘CLR’ is displayed.
The lowest DHW tank or Storage tank temperature since this item
was last cleared. To clear this item, press both the
and buttons
until ‘CLR’ is displayed.
0 to 255˚F
(-18 to 124˚C)
0 to 255˚F
(-18 to 124˚C)
• •
• •
• •
• •
363 Monitor Menu
Item
LTD
USER
Range
The highest outdoor air temperature recorded since this item was
last cleared. To clear this item, press and hold the and buttons
until ‘CLR’ is displayed.
The lowest outdoor air temperature recorded since this item was
last cleared. To clear this item, press and hold the
and buttons
until ‘CLR’ is displayed.