View Menu (1 of 1)
Outdoor Current outdoor air temperature as measured by the
outdoor sensor. This item is only available when Mix 1 Mode is set
to 1, Mix 2 Mode is set to 1 or the Boiler sensor Return / Supply DIP
switch is set to Supply.
-67 to 149°F
(-55 to 65°C)
E1
Mix 1 Supply Current mix 1 supply water temperature as measured
by the mix 1 supply sensor. This item is only available when Mix 1
Mode is set to 1.
14 to 266°F
(-10 to 130°C)
E1
Mix 1 Target Mix 1 target temperature is the temperature the control
is currently trying to maintain at the mix 1 supply sensor. This item is
only available when Mix 1 Mode is set to 1.
– – –
, 14 to 266°F
(
– – –
, -10 to 130°C)
E1
Mix 2 Supply Current mix 2 supply water temperature as measured
by the mix 2 supply sensor. This item is only available when Mix 2
Mode is set to 1 or 2.
14 to 266°F
(-10 to 130°C)
E1
Mix 2 Target Mix 2 target temperature is the temperature the control
is currently trying to maintain at the mix 2 supply sensor. This item is
only available when Mix 2 Mode is set to 1 or 2.
– – –
, 14 to 266°F
(
– – –
, -10 to 130°C)
B1
Boiler Supply Current boiler supply water temperature as measured
by the boiler sensor. This item is only available when the Boiler
Sensor Return / Supply DIP switch is set to Supply.
14 to 266°F
(-10 to 130°C)
B1
Boiler Target Boiler target temperature is the temperature the
control is currently trying to maintain at the boiler supply sensor. This
item is only available when the Boiler Sensor Return / Supply DIP
switch is set to Supply.
– – –
, 14 to 266°F
(
– – –
, -10 to 130°C)
B2
Boiler Return Current boiler return water temperature as measured
by the boiler sensor. This item is only available when the Boiler
Sensor Return / Supply DIP switch is set to Return.
14 to 266°F
(-10 to 130°C)
Display
Description
Range
Section
Installer
Adv