Vista de pagina 23
24 of 36
Copyright © D 362 - 12/08
362 Adjust Menu (3 of 4)
Actual
Setting
The time that the actuating motor requires to
operate from fully closed to fully open.
MIXING = FLOT
30 to 230 sec
Default = 160 sec
The location of the boiler sensor. This affects
operation of the boiler contact.
SUP (Supply)
RET (Return)
NONE
Default = SUP
The systems warm weather shut down during the
UnOccupied period.
DIP switch =
Setback
MODE = 1
Section
LTD
INST
ADV
Range
Access
Level
DescriptionItem Field
USER
The maximum T for the snow melting slab.
Boil SENS SUP MODE = 2
10 to 70˚F, OFF
(5 to 39˚C, OFF)
Default =40°F (22°C)
The maximum temperature allowed for the boiler
target temperature.
Boil SENS = SUP MODE = 1
120 to 225˚F, OFF
(49 to 107˚C, OFF)
Default = 210°F (99°C)
The minimum temperature allowed for the boiler
target temperature.
Boil SENS NONE
OFF, 80 to 180˚F
(OFF, 27 to 82˚C)
Default = 140°F (60°C)
The time delay the control can expect between
the time the boiler contact closes and the
burner fires.
Boil SENS = SUP
0:00 to 3:00 min
(1 sec. increments)
Default = 0:10 min
The thermal mass characteristics of the boiler that
is being used.
Boil SENS = SUP
LITE, MED, HEVY
Default = MED
The differential that the control is to use when it
is operating the boiler.
Boil SENS =
SUP MODE = 1
AUTO, 2 to 42˚F
(AUTO, 1 to 23˚C)
Default = AUTO
The differential for the snow melting system.
Boil SENS =
SUP
MODE = 2
AUTO, 2 to 42˚F
(AUTO, 1 to 23˚C)
Default = AUTO
35 to 100˚F, OFF
(2 to 38˚C, OFF)
Default =70°F (21°C)
Occ
35 to 100˚F, OFF
(2 to 38˚C, OFF)
Default =60°F (4°C)
UnOcc
The systems warm weather shut down during the
Occupied period.
A
D1
D2
D3
C1
D1
D1
D1
D1
D1
D1
B1
C4
B1
Vista de pagina 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 ... 35 36