© 2007 D 161 - 08/07 10 of 36
ADJUST MENU
ADJUST Menu (1 of 5)
Mode Item Field Range Access Description
1
2
3
4
1, 2, 3, 4
Default = 1
InST
ADV
APPLICATION MODE SECTION A, B, C, D
Select the application for the setpoint control.
1 = Setpoint
2 = Hot Tub
3 = DHW Tank
4 = Floor
2
HEAT, OFF
Default = HEAT
USEr
InST
ADV
MODE OF OPERATION SECTION B
Select to either heat or turn off the hot tub.
1
OFF, -4°F
(-20°C) to
Setpoint
Maximum
Default = 160°F
(71.0°C)
LTD
USEr
InST
ADV
SET SETPOINT OCCUPIED SECTION A
Select the setpoint temperature for the occupied period.
Note: In the Limited Access Level, the temperature can only
be adjusted by +/-3°F (1.5°C) from the temperature setting
entered prior to entering the Limited access level.
The ADJUST Menu items are the programmable
settings used to operate the mechanical equipment.
Continued on next page.