© 2007 D 161 - 08/07 32 of 36
Error Message Description
DIP SWITCH 2 MODE
The tN4 System Control DIP switch 2 is set to None and the setpoint control has detected a tN4
System Control. The setpoint control does not operate until this error is corrected. The tN4 System
Control DIP switch 2 must be set to tN4 System Control.
SETPOINT SENSOR SHORT CIRCUIT
Due to a short circuit, the setpoint control failed to read the sensor input. The setpoint control displays
the error and stops operation until the error message is cleared. Check the wire for short circuits.
Locate and repair the problem as described in the Data Brochure D 070. The error message clears
automatically once the error is corrected.
SETPOINT SENSOR OPEN CIRCUIT
Due to an open circuit, the setpoint control failed to read the sensor input. The setpoint control
displays the error and stops operation until the error message is cleared. Check for loose or broken
wires. Locate and repair the problem as described in the Data Brochure D 070. The error message
clears automatically once the error is corrected.
SCHEDULE MEMBER ERROR
The setpoint control can no longer detect its schedule master. Ensure that the Schedule Master
number has not been changed. Check the communication connections for open or short circuits.
Once the schedule master has been detected, the error message clears.
Error Messages (3 of 4)
Note: Error Messages are only visible while in the Advanced or Installer access level.