© 2007 D 162 - 08/07 10 of 32
ADJUST Menu (2 of 6)
Mode Item Field Range Access Description
2
OFF, 40°F
(4.5°C) to Hot Tub
Maximum
Default = 95°F
(35.0°C)
USEr
InST
ADV
SET HOT TUB UNOCCUPIED
SECTION B
Select the hot tub temperature for the unoccupied
period.
Note: This item is only available when a
programmable setback schedule has been
selected.
2
OFF, 40°F
(4.5°C) to Hot Tub
Maximum
Default = 50°F
(10.C)
USEr
InST
ADV
SET HOT TUB AWAY SECTION B
Select the hot tub temperature for the away
period.
Note:
This item is only available when scenes
are set to On.
3
OFF, 40°F (4.5°C)
to DHW Maximum
Default = 130°F
(54.5°C)
LTD
USEr
InST
ADV
SET DHW TANK OCCUPIED SECTION C
Select the indirect domestic hot water tank
temperature for the occupied period.
Note: In the Limited Access Level, the temperature
can only be adjusted by +/-3°F (1.5°C) from the
temperature setting entered prior to entering the
Limited access level.
3
OFF, 40°F (4.5°C)
to DHW Maximum
Default = 110°F
(43.5°C)
USEr
InST
ADV
SET DHW TANK UNOCCUPIED SECTION C
Select the indirect domestic hot water tank
temperature for the unoccupied period.
Note: This item is only available when a
programmable setback schedule has been
selected.
3
OFF, 40°F (4.5°C)
to DHW Maximum
Default = OFF
USEr
InST
ADV
SET DHW TANK AWAY SECTION C
Select the indirect domestic hot water tank
temperature for the away period.
Note:
This item is only available when scenes
are to set to On.
5
OFF, 40°F (4.5°C)
to Floor Maximum
Default = 80°F
(26.5°C)
LTD
USEr
InST
ADV
SET FLOOR OCCUPIED SECTION E
Select the floor temperature for the occupied
period.
Note: In the Limited Access Level, the temperature
can only be adjusted by +/-3°F (1.5°C) from the
temperature setting entered prior to entering the
Limited access level.
5
OFF, 40°F (4.5°C)
to Floor Maximum
Default = 70°F
(21.0°C)
USEr
InST
ADV
SET FLOOR UNOCCUPIED SECTION E
Select the floor temperature for the unoccupied
period.
Note: This item is only available when a
programmable setback schedule has been
selected.
5
OFF, 40°F (4.5°C)
to Floor Maximum
Default = OFF
USEr
InST
ADV
SET FLOOR AWAY
SECTION E
Select the floor temperature for the away
period.
Note: This item is only available when scenes
are set to On.
ADJUST MENU
Continued on next page.