Tekmar 262 Boiler Control Installation Manual de usuario Pagina 1

Busca en linea o descarga Manual de usuario para Sensores Tekmar 262 Boiler Control Installation. tekmar 262 Boiler Control Installation User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 36
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
1 of 36
Copyright © D 262 -12/08
D 262
12/08
Boiler Control 262
- Data Brochure
The Boiler Control 262 is a micro processor based control designed to maximize the comfort and efficiency of a hydronic heating system.
The control is designed to operate in two distinct modes.
MODE —1— (Two Stage Boiler & DHW) allows for the control of two separate on /off boiler stages (or one low / high fire) based on outdoor
air temperature, control for indirect Domestic Hot Water (DHW) generation and a Setpoint load. For single zone temperature control
with indoor temperature feedback, a Room Temperature Unit (RTU) or indoor sensor may be connected to the 262. Multiple zone
temperature control is achieved by using either a conventional thermostat system or by connecting a tekmar Zone Control to the 262.
MODE —2— is designed specifically for dedicated DHW applications. In Mode 2, the 262 can stage and rotate two on / off boiler stages
(or one low / high fire) in order to provide heat to a DHW storage system.
The 262 control includes a large Liquid Crystal Display (LCD) in order to view system status and operating information. The same LCD
is used when setting up and installing the control. Standard features include Equal Run Time Rotation, intelligent boiler operation, digital
temperature readouts, and pump exercising. With the addition of a monitoring feature, it is now possible to track pump and boiler running
hours, DHW tank temperature, outdoor and system high and low temperatures, boiler firing cycles, plus many other useful items.
Several energy saving features have been incorporated into the 262 such as Warm Weather Shut Down (WWSD), DHW post purge,
system setback, DHW priority and an automatic differential for boiler operation.
LR 58233
E150539
70
M
Input
120 V (ac)
Power
Supply
Input
Zone Control
Input
Indoor Sensor
Output
DHW Pump OR
DHW Valve
Input
tekmar
Timer
Output
Boiler System
Pump
Input
Slab Sensor
OR
OR
Output
Boiler
Output
Boiler
Input
Remote
Display
Module (RDM)
OR
Input
Room
Temperature
Unit (RTU)
ItemMenu
°
F
Vie
!
WWS
1
%%
2
ItemMenu
°
F
Vie
!
WWS
1
%%
2
Input
Setpoint
Demand
signal
Input
DHW Demand
signal
Input
Boiler
Demand
signal
Input
Universal
Sensor
Included
Input
Universal
Sensor
Optional
Input
Outdoor
Sensor
Included
2
1
°
F
View
7
Power 115 V
±
10% 60 Hz 900 VA
Relays 230 V (ac) 7.5 A 1/3 hp, pilot duty 240 VA
Demands 20 to 260 V (ac) 2 VA
Made in Canada by
tekmar Control Systems Ltd.
tektra 929-03
Test
not testing
testing
off
red
red
231
Com
Dem
4
10
Boiler
Boil
P1
Power
Boiler Control 262
Two Stage Boiler & DHW / Two Stage DHW
Signal wiring must be rated at least 300 V.
Wiring must be rated 194°F (90°C) minimum
6
9
DHW
Pmp / Vlv
DHW
Dem
Setp
Dem
5
12
Stage
11
NL
8
For maximum heat,
press and hold
Test
button for 3 seconds.
Operating Modes
1 Two Stage Boiler & DHW
2 Two Stages for DHW
14
Stage
13
Boiler Demand
DHW Demand
Setpoint Demand
WWSD
Minimum
Maximum
11 2 2
Reset Ratio
Setback
Characterized
Heating Curve
None
Menu
Item
1
Note:
Boiler, DHW, or setpoint
demand must be powered
with 20 to 260 V (ac)
before the boiler is able
to fire.
Meets Class B:
Canadian ICES
FCC Part 15
H1109F
Date Code
See product literature
INSTALLATION CATEGORY II
16
DHW
17
Com
18 19
10K Out
20
tN1/
tN2
15
UnO
Sw
21 22
Boil
Com
Do not apply power
Vista de pagina 0
1 2 3 4 5 6 ... 35 36

Indice de contenidos

Pagina 1 - - Data Brochure

1 of 36Copyright © D 262 -12/08D 26212/08Boiler Control 262- Data BrochureThe Boiler Control 262 is a micro processor based control designed to maximi

Pagina 2 - Table of Contents

10 of 36Copyright © D 262 -12/082) as described in Section B1. With the RTU connected, the 262 measures the actual ROOM temperature. Indoor temperatu

Pagina 3

11 of 36Copyright © D 262 -12/08Sequence, Section C2Internal Demand (DHW SENS = DHW) If the control receives a DHW demand from a DHW sensor attached t

Pagina 4 - Section D

12 of 36Copyright © D 262 -12/08Section C3 —DHW with Low Temperature Boilers (Mode = —1—)If DHW is to be incorporated into a low temperature system su

Pagina 5 - 672 hours

13 of 36Copyright © D 262 -12/08Section D1—General Setpoint Operation (Mode = —1—)The 262 can handle setpoint loads which are high temperature loads c

Pagina 6 - Section B1

14 of 36Copyright © D 262 -12/08InstallationCAUTIONImproper installation and operation of this control could result in damage to the equipment and pos

Pagina 7 - Heating Curve

15 of 36Copyright © D 262 -12/08Boiler DemandTo generate a Boiler Demand, a voltage between 24 V (ac) and 240 V (ac) must beapplied across the Boiler

Pagina 8

16 of 36Copyright © D 262 -12/08DHW SensorConnect the two wires from the DHW Sensor 071 to the Com and DHWterminals (19 and 20). The DHW Sensor is use

Pagina 9 - Slab Max

17 of 36Copyright © D 262 -12/08Test the Power Supply Make sure exposed wires and bare terminals are not in contact with otherwires or grounded surfac

Pagina 10 - Storage Tank

18 of 36Copyright © D 262 -12/08Connecting the Control Make sure all power to the devices and terminal blocks is off and remove anyremaining jumpers f

Pagina 11 - Copyright © D 262 -12/08

19 of 36Copyright © D 262 -12/08Access LevelsThe tekmar Boiler Control 262 comes with four Access Level settings.These Access Levels restrict the numb

Pagina 12 - 12 of 36

2 of 36Copyright © D 262 -12/08How To Use The Data BrochureThis brochure is organized into four main sections. They are: 1) Sequence of Operation, 2)

Pagina 13 - Setpoint

20 of 36Copyright © D 262 -12/08Minimum boiler supply temperature during a setpointdemand.MODE = —1—262 View Menu (1 of 1)-31 to 266˚F(-35 to 130˚C)-

Pagina 14 - Installation

21 of 36Copyright © D 262 -12/08 Section• • • •• • •• • •• •• ••• •• •262 Adjust Menu (1 of 4)The desired room air temperature during anOccupied perio

Pagina 15 - Output Connections

22 of 36Copyright © D 262 -12/08 Section262 Adjust Menu (2 of 4)• •The design supply water temperature used in theheat loss calculations for the heati

Pagina 16 - Timer Switch

23 of 36Copyright © D 262 -12/08 Section262 Adjust Menu (3 of 4)• • •• • •The DHW storage tank’s temperature during theOccupied period.DHW SENS = DHWD

Pagina 17 - 24 to 240 V (ac)

24 of 36Copyright © D 262 -12/08 Section• • • •The type of setback override that is in effect.DIP switch = SetbackAWAY is available even if DIP ≠ Setb

Pagina 18 - DIP Switch Settings

25 of 36Copyright © D 262 -12/08ItemMenuUnOcc 1°FViewHeatRoom Temperature Units (RTUs) 062 and 063A single RTU may be connected to the Boiler Control

Pagina 19 - Access Levels

26 of 36Copyright © D 262 -12/08262 RTU Monitor Menu (1 of 1)The highest outdoor air temperature recorded since thisitem was last cleared.To clear, pr

Pagina 20 - Section

27 of 36Copyright © D 262 -12/08Testing the ControlThe Boiler Control 262 has a built in test routine which is used to test the main control functions

Pagina 21

28 of 36Copyright © D 262 -12/08TroubleshootingWhen troubleshooting any heating system, it is always a good idea to establish a set routine to follow.

Pagina 22 - Equal Run Time Rotation

29 of 36Copyright © D 262 -12/08Sketch the piping of the system. This is a relatively simple step that tends to be overlooked,however it can often sav

Pagina 23 - 23 of 36

3 of 36Copyright © D 262 -12/08ecafretnI resUSymbol DescriptionDisplayBoiler DemandDHW DemandSetpoint DemandWWSDMinimumMaximumMenuItemNumber FieldDisp

Pagina 24

30 of 36Copyright © D 262 -12/08262 Monitor Menu (2 of 3)The total number of Boiler Pump (P1) running hours sincethis item was last cleared.The highes

Pagina 25 - • • • • •

31 of 36Copyright © D 262 -12/08262 Error Messages (1 of 4)Error Displayed Description of ErrorThe control was unable to store a piece of information

Pagina 26 - UP & DOWN

32 of 36Copyright © D 262 -12/08rorrE fo noitpircseDdeyalpsiD rorrE262 Error Messages (2 of 4)The control was unable to read a piece of information st

Pagina 27

33 of 36Copyright © D 262 -12/08The control is no longer able to read the Outdoor sensor due to an open circuit. In this case the controlassumes an ou

Pagina 28 - Operation

34 of 36Copyright © D 262 -12/08The Remote Sensor 3 attached to the RTU is being read as an open circuit. The RTU will continueoperation using all rem

Pagina 29 - Piping in the

35 of 36Copyright © D 262 -12/08Notes

Pagina 30 - DescriptionItem Field

Technical DataThe installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise.Con

Pagina 31 - 262 Error Messages (1 of 4)

4 of 36Copyright © D 262 -12/08Section A —General OperationPOWERING UP THE CONTROL When the Boiler Control 262 is powered up, the control displays the

Pagina 32 - 262 Error Messages (2 of 4)

5 of 36Copyright © D 262 -12/08Sequence, Section ALight (LITE) The LITE setting is selected if the boiler(s) that is used has a low thermal mass. This

Pagina 33 - 262 Error Messages (3 of 4)

6 of 36Copyright © D 262 -12/08External Unoccupied An external signal can place the 262 into an UnOccupied mode. Any time the UnO Sw (18)and the Com S

Pagina 34 - 262 Error Messages (4 of 4)

7 of 36Copyright © D 262 -12/08BOILER START (Boil STRT) (RESET RATIO) The Boil STRT temperature is the boiler supply water temperature that theheating

Pagina 35 - 35 of 36

8 of 36Copyright © D 262 -12/08ROOM OCC & UNOCC (ROOM) (CHARACTERIZED HEATING CURVE)The ROOM is the desired room temperature for the boiler zone(s

Pagina 36 - Technical Data

9 of 36Copyright © D 262 -12/08Boosting (BOOST) When the control changes from the UnOccupied to the Occupied mode,it enters into a Boosting mode. In t

Comentarios a estos manuales

Sin comentarios